• DESCRIPTION
  • TECHNICAL DATA
  • DOWNLOAD
  • Multiprotocol Module with a MIX of I/O's - the Ultimate Controller Extension
    The most versatile I/O module with 38 inputs and outputs, offering the most cost-effective price per point ratio. Powerful I/O module that works as a remote or distributed I/O over IP with open protocols: BACnet IP, and Modbus TCP/IP. Open protocols standard offers the versatility of installing the modules in both new and existing facilities, whether it is a system expansion or a retrofit. The most popular types of inputs and outputs are MIXed in a space-saving design and allow the module to be a versatile controller extension, whether in a small or large facility.

    8 Universal Inputs
    Support for over 20 types of temperature sensors and voltage, resistance, current, and dry contact measurements on each universal input.

    12 Digital Inputs
    Dry contact inputs - made for monitoring. 100 Hz fast pulse counter with override function saves the real-time values to the EEPROM memory.

    12 Digital Outputs
    Digital outputs equipped with normally open 3 A relays allow for direct control without additional relays.

    6 Analog Outputs
    0-10 V DC control with 10 mA accuracy, PWM modes, and a maximum load of up to 20 mA to power external relays makes the output suitable for a variety of scenarios.

    Modbus TCP/IP to Modbus RTU/ASCII Gateway
    Built-in Modbus gateway on the COM1 port enables integration of up to 128 Modbus slave devices to the IP layer.

    Simplified Configuration and Commissioning Process
    The module allows for seamless configuration over BACnet, Modbus, built-in web server, or dedicated free of charge tool. The ability to be powered from a USB port facilitates local testing and a straightforward updating process. Two Ethernet ports working in a switch mode allow for daisy chaining of multiple modules over the RJ45, which facilitates the cabling process and reduces engineering time.

    Quality and Reliability Confirmed by Certificates
    iSMA CONTROLLI is a long-standing member of the BACnet community. The experience in developing high quality products and the BTL (BACnet Test Laboratory) certification confirm the excellent performance of communication using the BACnet protocol.
    Reliability of operation is confirmed by UL testing, certified by Underwriters Laboratories.


     

    Technical Specification

     

    Hardware Specification
    2 Ethernet interface with built-in switch
    RS485 interface
    mini USB type B interface
    Status LED indicators
    DIN rail mounted
    38 I/Os onboard

    Inputs
    8 Universal Inputs (UI)
    Temperature input in Celcius degrees: 10K3A1, 10K4A1, Carel 10K, 20K6A1, 2.2K3A1, 3K3A1, 30K6A1, SIE1, TAC1, SAT1, Pt1000, Ni1000 0C, Ni 1000 20C, Ni1000 LG 2
    Temperature input in Fahrenheit degrees: 10K Type2, 10K type3, 20K, 3K, PT 1000, Ni 1000 32F, Ni 1000 70F
    Resistive input 0-1000 kΩ
    Voltage input 0-10 V DC
    Current input 0-20 mA
    Dry contact input

    12 Digital Inputs (DI)
    Dry contact inputs
    Fast pulse counter up to 100 Hz save in EEPROM memory

    Outputs
    12 Digital Outputs (DO)
    NO relay output
    Resistive load max. 3 A @ 230 V AC / 30 V DC
    Inductive load max. 75 VA @ 230 V AC / 30 W @ 30 V DC

    6 Analog Outputs (AO)
    Output 0-10 V DC maximum load up to 20 mA
    PWM: 0.01 Hz, 0.1 Hz, 1 Hz, 10 Hz, 100 Hz

    Communication
    BACnet IP
    Modbus TCP/IP
    Modbus TCP/IP to Modbus RTU/ASCII Gateway
    Free software iSMA Configurator
    Built-in web server
    Dedicated Niagara Framework modules

    Power Supply
    24 V DC ± 20%
    24 V AC ± 20%

    More Information
    Outputs typeAnalog, Digital
    Inputs typeUniversal, Digital
    Communication protocolBACnet IP, Modbus TCP/IP, Modbus TCP/IP to Modbus RTU/ASCII Gateway
    Power supply24 V AC, 24 V DC
    IP40
    Digital inputs12
    Analog outputs6
    Digital outputs12